F. P. Mohamed
Method to discard partial discharge (PD) pulses from neighboring high voltage equipment.
Mohamed, F. P.; Siew, W. H.; Strachan, S. S.; Ayub, A. S.; Mclellan, K.
Authors
W. H. Siew
S. S. Strachan
A. S. Ayub
K. Mclellan
Abstract
On-line partial discharge (PD) diagnostics data are corrupted by various noise sources and this makes it more challenging to extract the PD signal contained in the raw data. Though the noise sources can be filtered out using signal processing techniques, PDs from neighboring cables and other high voltage equipment make the de-noising process more difficult due to the similar features of these signals with the PD signal of interest. Proposed in this paper is a double-ended partial discharge diagnostic system with dual sensors at each end which uses wireless time triggering using global time reference with the aid of global positioning system (GPS). Using the time of arrival method based on the velocity of propagation on the data, PD pulses originating from other sources can be discarded which reduces the volume of data to be stored and would eventually also reduce the hardware and software requirements of the denoising process thereby improving de-noising efficiency. System design, laboratory tests and on-site measurements are discussed.
Citation
MOHAMED, F.P., SIEW, W.H., STRACHAN, S.S., AYUB, A.S. and MCLELLAN, K. 2015. Method to discard partial discharge (PD) pulses from neighboring high voltage equipment. High voltage engineering [online], 4, pages 1125-1131. Available from: http://caod.oriprobe.com/articles/44523683/Method_to_Discard_Partial_Discharge_Pulses_from_Neighboring_High_Volta.htm
Journal Article Type | Article |
---|---|
Acceptance Date | Nov 4, 2014 |
Online Publication Date | Apr 1, 2015 |
Publication Date | Apr 1, 2015 |
Deposit Date | Sep 8, 2020 |
Publicly Available Date | Sep 8, 2020 |
Journal | High voltage engineering |
Print ISSN | 1003-6520 |
Electronic ISSN | 1003-6520 |
Publisher | High Voltage Engineering Publishers |
Peer Reviewed | Peer Reviewed |
Volume | 2015 |
Issue | 4 |
Pages | 1125-1131 |
Keywords | Partial discharges, Time domain reflectometry; Time synchronization |
Public URL | https://rgu-repository.worktribe.com/output/844516 |
Publisher URL | http://caod.oriprobe.com/articles/44523683/Method_to_Discard_Partial_Discharge_Pulses_from_Neighboring_High_Volta.htm |
Files
AYUB 2015 Method to discard
(815 Kb)
PDF
Publisher Licence URL
https://creativecommons.org/licenses/by-nc/4.0/
You might also like
A study of zero bid wind farm for future Scotland’s energy demands: a new approach.
(2022)
Journal Article
Lightning protection methods for wind turbine blades: an alternative approach.
(2020)
Journal Article
Potential of floating solar technology in Malaysia.
(2019)
Journal Article
Downloadable Citations
About OpenAIR@RGU
Administrator e-mail: publications@rgu.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2025