Paul Tuohy
Lessons from post-occupancy evaluation and monitoring of the first certified passive house in Scotland.
Tuohy, Paul; Murphy, Gavin; Deveci, Gokay
Abstract
This paper describes an investigation carried out to understand the performance in practice of the first certified Passive House in Scotland and associated low or zero carbon technologies LZCT. The aim was to provide some useful feedbacks on actual performance in order to inform and hopefully improve building industry processes and policy. Monitoring was carried out on three dwellings on the west coast of Scotland. All dwellings are within 250m of each other with similar orientation and occupancy but were built to different standards representative of: 1950s Scottish building standards; 2010 Scottish building standards; and Passive House standards. The Passive House included mechanical ventilation with heat recovery (MVHR), air to air heat pump and solar thermal hot water heating LZCT systems which are in general being encouraged for new build and retrofit. The monitoring was carried out over 1 year and included indoor environment (RH, CO2, T), outdoor conditions (Solar, T, RH), energy use (Watts, kWh), operation schedules, and hot water system temperatures (T). In parallel with the monitoring, the Passive House and associated LZCT were investigated by inspection and observation and by comparison with both the Passive House Planning Package (PHPP) and the recommendations of the Certified Passive House Designer course. There were many interesting findings from the investigation, these included: lower and more consistent CO2 levels in the Passive House than in the houses without MVHR; poor layout and ducting of MVHR system giving poor energy performance and condensation problems; poor controls and specification of air to air heat pump giving poor space heating performance; poor control of solar thermal hot water system reducing performance; lack of occupant understanding of operation and maintenance for the LZCT systems. The lessons learned are relevant to all future implementations of these LZCT systems in the building stock both new build and retrofit. Possible improvements in industry and Passive House processes are discussed.
Citation
TUOHY, P., MURPHY, G. and DEVECI, G. 2012. Lessons from post-occupancy evaluation and monitoring of the first certified passive house in Scotland. In Proceedings of the 2012 PassivhusNorden conference: from low energy buildings to plus energy developments, 21-23 October 2012, Trondheim, Norway. Trondheim: TAPIR Akademisk Forlag.
Presentation Conference Type | Conference Paper (published) |
---|---|
Conference Name | 2012 PassivhusNorden conference |
Start Date | Oct 21, 2012 |
End Date | Oct 23, 2012 |
Acceptance Date | Oct 21, 2012 |
Publication Date | Dec 31, 2012 |
Deposit Date | Dec 17, 2013 |
Publicly Available Date | Dec 17, 2013 |
Publisher | TAPIR Akademisk Forlag |
Peer Reviewed | Peer Reviewed |
ISBN | 9788232101733 |
Keywords | Passive house; Passivhaus; Ecological footprint; Buildings and energy |
Public URL | http://hdl.handle.net/10059/911 |
Contract Date | Dec 17, 2013 |
Files
TUOHY 2012 Lessons from post occupancy
(264 Kb)
PDF
Publisher Licence URL
https://creativecommons.org/licenses/by-nc-nd/4.0/
You might also like
Development and pilot evaluation of an online retrofit decision-making tool for homeowners.
(2022)
Journal Article
Explorations in urban resilience for a post-hydrocarbon economy.
(2016)
Journal Article
Downloadable Citations
About OpenAIR@RGU
Administrator e-mail: publications@rgu.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2025
Advanced Search